{"id":2209,"date":"2015-02-02T17:36:30","date_gmt":"2015-02-02T22:06:30","guid":{"rendered":"https:\/\/www.hidrasoftware.com\/?p=2209"},"modified":"2015-02-02T22:24:49","modified_gmt":"2015-02-03T02:54:49","slug":"estimating-water-hammer-generated-by-the-unexpected-stoppage-of-a-water-pumping-station-with-ariete","status":"publish","type":"post","link":"https:\/\/www.hidrasoftware.com\/en\/estimating-water-hammer-generated-by-the-unexpected-stoppage-of-a-water-pumping-station-with-ariete\/","title":{"rendered":"Estimating Water Hammer generated by the Unexpected Stoppage of a Water Pumping Station with Ariete"},"content":{"rendered":"<p>When it comes to the significant effects of water hammer in water conveying pipelines (water pumping mains), the situation of accidental stoppage of flow supplied by a pumping station is the one that represents, perhaps, the most unfavorable condition in the design and operation of the system.<\/p>\n<p>This accidental stoppage of the equipment within a pumping station is usually caused by the unexpected power supply failure to their engines, generating there from pressure surges in the system that usually reach considerable magnitudes, thus compromising both the station and pipeline\u2019s components physical integrity.<\/p>\n<p>We will see in this article how Ariete offers a practical approach to estimating and comparing those surge pressures generated on a pumping pipeline system by water hammer occurrence when the failure of equipment in a pumping station takes place.<\/p>\n<h2>Pipeline\u2019s Longitudinal Profile Creation<\/h2>\n<p>We have defined the <a href=\"https:\/\/www.hidrasoftware.com\/en\/creating-the-pipelines-longitudinal-profile-for-water-hammer-calculation-with-ariete\/\">Pipeline characteristics<\/a> by entering the following information at the <strong>Pipeline Data dialog<\/strong>:<\/p>\n<p><img decoding=\"async\" class=\"aligncenter size-full wp-image-3971\" title=\"Water-hammer-example-pipeline-data width=\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/01_Water-hammer-example-pipeline-data.png\" alt=\"Water-hammer-example-pipeline-data\" height=\"561\" \/><\/p>\n<p>In addition, for the pipeline, in the case of the maximum allowable pressures that pipes can withstand, we have followed the steps <a href=\"https:\/\/www.hidrasoftware.com\/en\/water-pipeline-design-with-ariete-maximum-allowable-working-pressures\/\">related in this article<\/a> in order to define piezometric head envelopes at steady flow conditions as well as at unsteady flow conditions<\/strong>, considering the case of cast iron pipes.<\/p>\n<h2>Pipeline\u2019s Upstream Device: Pumping Station<\/h2>\n<p>The Pipeline\u2019s water supplier Pumping Station to analyze in this water hammer calculation will consist of four similar Centrifugal Pumps with the characteristics summarized in the <strong>Pumping Station dialog<\/strong><strong>\u2192<\/strong><strong>Data tab<\/strong>:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3972\" title=\"Water-hammer-example-pumping-station-data\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/02_Water-hammer-example-pumping-station-data.png\" alt=\"Water-hammer-example-pumping-station-data\" width=\"667\" height=\"527\" \/><\/p>\n<p>Since what we want to model is the sudden failure of the equipment at the Pumping Station, we have activated the Use <a href=\"https:\/\/www.hidrasoftware.com\/en\/pumping-station-with-centrifugal-pumps-minimum-required-data-for-its-modeling-with-ariete-the-water-hammer-software\/#fichaoperacionEB\">Pumps\u2019Inertia<\/a> option to set 10 seconds from the simulation\u2019s beginning as the starting rundown time. This will also make it possible to display the results during the first 10 seconds prior to the unsteady flow occurrence (Water Hammer pre-startup).<\/p>\n<p><strong>Operation tab<\/strong> at Pumping Station dialog is configured as follows:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3973\" title=\"Pumping-station-operational-data-for-water-hammer-calculation\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/03_Pumping-station-operational-data-for-water-hammer-calculation.png\" alt=\"Pumping-station-operational-data-for-water-hammer-calculation\" width=\"532\" height=\"350\" \/><\/p>\n<h2>Pipeline\u2019s Downstream Device: Reservoir<\/h2>\n<p>The Pumping Pipeline in this water hammer <strong>example will be supplying to a fixed water level Reservoir (256 masl)<\/strong>, along the simulation time, for which we have created the respective device from the <strong>Devices menu<\/strong> and entered constant water level value:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3974\" title=\"Downstream-device-in-water-hammer-calculation-example\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/04_Downstream-device-in-water-hammer-calculation-example.png\" alt=\"Downstream-device-in-water-hammer-calculation-example\" width=\"779\" height=\"614\" \/><\/p>\n<p>We now have all the information set for the water hammer calculation of the pumping pipeline system, so let&#8217;s begin!<\/p>\n<h2>Getting Envelopes of Water Hammer\u2019s Maximum and Minimum Piezometric Heads<\/h2>\n<p><strong>To perform the water hammer calculation with Ariete<\/strong>, simply click the <strong><em>Starts Unsteady State Calculation<\/em><\/strong> button from the software\u2019s toolbar:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3975\" title=\"Starting-the-water-hammer-calculation\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/05_Starting-the-water-hammer-calculation.png\" alt=\"Starting-the-water-hammer-calculation\" width=\"365\" height=\"167\" \/><\/p>\n<p>After a few seconds, the water hammer\u2019s piezometric head envelopes (Max. and Min) will be shown in the Ariete\u2019s main window:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3976\" title=\"Piezometric-head-envelopes-water-hammer-example\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/06_Piezometric-head-envelopes-water-hammer-example.png\" alt=\"Piezometric-head-envelopes-water-hammer-example\" width=\"900\" height=\"519\" \/><\/p>\n<p>In which we see that <strong>the maximum calculated envelope is entirely below the envelope of Max. Allowable Piezometric Head<\/strong> (the one that the pipe can withstand, based on its Nominal Pressure), therefore not requiring the use of water hammer control devices at this level.<\/p>\n<h2>Visualizing Results at Specific Points In the Pipeline<\/h2>\n<p>In Ariete, it is possible to visualize results in tables and charts, along the chosen simulation time, for each of the control points in which the pipeline has been divided (there are 30 in this example).<\/p>\n<p>To see the results, we must select the control point in question, by clicking on it at the pipeline\u2019s Longitudinal Profile, and instantly view the hydraulic results, for the actual time step, in the <strong>Results panel<\/strong>:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3977\" title=\"Visualizing-water-hammer-results-at-Ariete-results-panel\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/07_Visualizing-water-hammer-results-at-Ariete-results-panel.png\" alt=\"Visualizing-water-hammer-results-at-Ariete-results-panel\" width=\"838\" height=\"743\" \/><\/p>\n<p>To display the results charts, for example, the piezometric head at the selected control point, <strong><em>click on the Piezometric Head option under the Charts and Tables button<\/em><\/strong>:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3978\" title=\"Water-hammer-Piezometric-head-at-control-points\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/08_Water-hammer-Piezometric-head-at-control-points.png\" alt=\"Water-hammer-Piezometric-head-at-control-points\" width=\"900\" height=\"587\" \/><\/p>\n<h2>Creating Combined Charts to Perform the Water Hammer Results Analysis<\/h2>\n<p>Another possibility, when results charts presentation is done with Ariete, is to choose, <strong>for the selected control point as referred in the previous section, another hydraulic parameter to be presented in the same chart but based in a secondary <\/strong><strong>\u201c<\/strong><strong>Y<\/strong><strong>\u201d<\/strong> <strong>axis.<\/strong><\/p>\n<div class=\"su-quote su-quote-style-default\"><div class=\"su-quote-inner su-u-clearfix su-u-trim\">\n<p>Let\u2019s suppose that you want to display, together with the pressure head at the control point, the air volume evolution, along the simulation time, of the vapor cavity generated by water hammer (column separation phenomenon) at that point.<\/p>\n<\/div><\/div>\n<p><em>We will click on the <strong>Charts and Tables button<\/strong> at the Results panel and select the <strong>Pressure<\/strong> option<\/em>. The chart is presented in the <strong>Ariete<\/strong><strong>\u2019<\/strong><strong>s Results Chart dialog:<\/strong><br \/>\n<img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3979\" title=\"Creating-combined-results-charts-for-water-hammer-analysis\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/09_Creating-combined-results-charts-for-water-hammer-analysis.png\" alt=\"Creating-combined-results-charts-for-water-hammer-analysis\" width=\"864\" height=\"981\" \/><\/p>\n<p>Note that in this dialog appears the \u201c<strong>Include Other Results<\/strong><strong>\u201d<\/strong> <strong>panel,<\/strong> from which <strong>you can select not only another field or result to include in this chart for the same point<\/strong>, but <strong>can also include fields from another control point<\/strong>, selected according to its chainage within the pipeline\u2019s length.<\/p>\n<p><strong>To add the volume of Air Volume field in this control point results chart<\/strong>, simply <em>select this parameter from the<\/em> \u201c<strong>Field to include<\/strong><strong>\u201d<\/strong> <strong>list<\/strong> and <em>click<\/em> <em>the<\/em><strong> Add Field button<\/strong>:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3980\" title=\"Creating-combined-results-charts-for-water-hammer-analysis-Air-Volume\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/10_Creating-combined-results-charts-for-water-hammer-analysis-Air-Volume.png\" alt=\"Creating-combined-results-charts-for-water-hammer-analysis-Air-Volume\" width=\"864\" height=\"596\" \/><\/p>\n<p>Thus, within our own Pipeline\u2019s Water Hammer analysis, we will be able to establish that, in the specific case of the chainage 5373 m, cavitation (water column separation) starts approximately in second 18 from the simulation\u2019s starting time, keeping this condition until second 29.<\/p>\n<div class=\"su-note\"  style=\"border-color:#167dc1;border-radius:3px;-moz-border-radius:3px;-webkit-border-radius:3px;\"><div class=\"su-note-inner su-u-clearfix su-u-trim\" style=\"background-color:#3097DB;border-color:#fcffff;color:#FFFFFF;border-radius:3px;-moz-border-radius:3px;-webkit-border-radius:3px;\">\nIt is also possible, provided the consistency with the existing units of the graph is kept, to add more fields of results to the current chart. For example: To display the piezometric head evolution (consistent with the primary Y axis units) at the current point, only select that field and add it to the chart:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3981\" title=\"Creating-combined-results-charts-for-water-hammer-analysis-Piezometric-head\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/11_Creating-combined-results-charts-for-water-hammer-analysis-Piezometric-head.png\" alt=\"Creating-combined-results-charts-for-water-hammer-analysis-Piezometric-head\" width=\"600\" height=\"414\" \/><br \/>\n<\/div><\/div>\n<h2>Presenting the Water Hammer Calculation results in Tables<\/h2>\n<p>Finally, the results at any control point and along the selected total simulation time can be presented by <strong><em>selecting the Table option<\/em><\/strong> inside the <strong><em>Charts and Tables button in the Results panel<\/em><\/strong>:<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"aligncenter size-full wp-image-3982\" title=\"water-hammer-calculation-results-in-tables\" src=\"https:\/\/www.hidrasoftware.com\/wp-content\/uploads\/2015\/02\/12_water-hammer-calculation-results-in-tables.png\" alt=\"water-hammer-calculation-results-in-tables\" width=\"735\" height=\"899\" \/><\/p>\n<p>From which you can not only print the results table, but also copy the data to the windows clipboard for use in software such as Microsoft Excel\u00ae.<\/p>\n<p>Thus, the pumping pipeline\u2019s Water Hammer results analysis becomes easier using a practical and simple tool like Ariete. <a href=\"https:\/\/www.hidrasoftware.com\/en\/download\/#ariete\">Give it a try<\/a>!<\/p>\n<p>&nbsp;<\/p>\n","protected":false},"excerpt":{"rendered":"<p>When it comes to the significant effects of water hammer in water conveying pipelines (water pumping mains), the situation of accidental stoppage of flow supplied by a pumping station is the one that represents, perhaps, the most unfavorable condition in the design and operation of the system.<\/p>\n","protected":false},"author":1,"featured_media":2210,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[119],"tags":[125,124],"class_list":["post-2209","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-water-hammer","tag-pumping-mains","tag-pumping-station","post-wrapper","thrv_wrapper"],"aioseo_notices":[],"_links":{"self":[{"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/posts\/2209","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/comments?post=2209"}],"version-history":[{"count":4,"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/posts\/2209\/revisions"}],"predecessor-version":[{"id":2367,"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/posts\/2209\/revisions\/2367"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/media\/2210"}],"wp:attachment":[{"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/media?parent=2209"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/categories?post=2209"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.hidrasoftware.com\/en\/wp-json\/wp\/v2\/tags?post=2209"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}